Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100023 C01 |
Issuance Date |
2015-06-02 |
Current Penalty |
2040.0 |
Initial Penalty |
3400.0 |
Final Order |
2015-06-16 |
Nr Instances |
1 |
Nr Exposed |
1 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards: (a) Storage Above Office - On or about March 10, 2015, the open sided floor above the office was not guarded by standard guard rails. |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100253 B02 II |
Issuance Date |
2015-06-02 |
Current Penalty |
2040.0 |
Initial Penalty |
3400.0 |
Final Order |
2015-06-16 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.253(b)(2)(ii): Assigned storage spaces for cylinders was not located away from elevators, stairs, or gangways where cylinders could not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons: (a) Rear of Plant - On or about March 10, 2015 oxygen, acetylene and other LP gas cylinders were not secured to prevent them from being knock over. |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100253 B04 III |
Issuance Date |
2015-06-02 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-06-16 |
Nr Instances |
1 |
Nr Exposed |
2 |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet: (a) Rear of the Plant - Oxygen and Acetylene was stored together. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19040029 A |
Issuance Date |
2015-06-02 |
Abatement Due Date |
2015-06-23 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-06-16 |
Nr Instances |
1 |
Nr Exposed |
18 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1904.29(a): The employer did not use an OSHA 300, 301 and 300A Form or equivalent. (a) Meridian Location - On or about March 10, 2015 the employer was not maintaining the OSHA 300 - A for the previous years of 2012, 2013 and 2014. Abatement Certification and Documentation is required |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100303 G01 III |
Issuance Date |
2015-06-02 |
Abatement Due Date |
2015-06-23 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-06-16 |
Nr Instances |
1 |
Nr Exposed |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(1)(iii): The employer did not ensure that at least one entrance of sufficient area was provided to give access to the working space about electric equipment 600 Volts, nominal, or less. (a) Maintenance Shop - On or about March 10, 2015, the Ingersoll Rand Air Compressor and the dryer were located in a manner that blocked access to the electrical breaker box. |
|
Citation ID |
02003A |
Citaton Type |
Other |
Standard Cited |
19101200 F05 I |
Issuance Date |
2015-06-02 |
Abatement Due Date |
2015-06-23 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-06-16 |
Nr Instances |
1 |
Nr Exposed |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(f)(5)(i): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein: (a)Welding Operation - On or about March 11, 2015 the garden sprayer containing mineral spirit was not labeled with the identity of the product contained therein. |
|
Citation ID |
02003B |
Citaton Type |
Other |
Standard Cited |
19101200 F05 II |
Issuance Date |
2015-06-02 |
Abatement Due Date |
2015-06-23 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2015-06-16 |
Nr Instances |
1 |
Nr Exposed |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(f)(5)(ii): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the appropriate hazard warnings: (a)Welding Area - on or about March 11, 2015 the employer had not labeled the garden sprayer containing mineral spirits with the appropriate hazard warning. |
|