Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2016-04-26
|
Case Closed |
2016-06-29
|
Related Activity
Type |
Complaint |
Activity Nr |
1084237 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100023 C01 |
Issuance Date |
2016-06-08 |
Abatement Due Date |
2016-06-16 |
Current Penalty |
3780.0 |
Initial Penalty |
6300.0 |
Final Order |
2016-06-27 |
Nr Instances |
1 |
Nr Exposed |
7 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards: (a) Roof above the ABC room - On or about March 19, 2016 five (5) employees clearing flour off the roof by shoveling it over the edge to the ground below were exposed to a 25 foot fall hazard. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100303 B07 I |
Issuance Date |
2016-06-08 |
Abatement Due Date |
2016-06-10 |
Current Penalty |
3780.0 |
Initial Penalty |
6300.0 |
Final Order |
2016-06-27 |
Nr Instances |
1 |
Nr Exposed |
14 |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: (a) ABC Area - On or about April 26, 2016 electrical panel breaker cabinet has exposed energized electrical components not protected from accidental contact exposing employees to electrical shock. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100303 B07 IV |
Issuance Date |
2016-06-08 |
Abatement Due Date |
2016-06-10 |
Current Penalty |
2805.0 |
Initial Penalty |
4675.0 |
Final Order |
2016-06-27 |
Nr Instances |
1 |
Nr Exposed |
17 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of electric equipment, such as parts that were broken, bent, cut or deteriorated by corrosion, chemical action, or overheating: (a) Blend Department - On or about May 17, 2016 employees operating blending machine "D" while the electrical power supply line is broken causing short at control switch. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100303 G01 |
Issuance Date |
2016-06-08 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2016-06-27 |
Nr Instances |
1 |
Nr Exposed |
14 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: (a) ABC electrical room - On or about April 26, 2016 the electrical panels on back wall was blocked by tool chest preventing access for safe operation and maintenance. |
|
|