Inspection Type |
Complaint
|
Scope |
Complete
|
Safety/Health |
Safety
|
Close Conference |
2013-05-01
|
Case Closed |
2014-05-30
|
Related Activity
Type |
Complaint |
Activity Nr |
815350 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100106 D06 I |
Issuance Date |
2013-07-01 |
Abatement Due Date |
2013-08-16 |
Current Penalty |
2800.0 |
Initial Penalty |
2800.0 |
Final Order |
2013-09-17 |
Nr Instances |
8 |
Nr Exposed |
8 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(d)(6)(i): "General." Storage outside buildings shall be in accordance with Table H-16 or H-17, and subdivisions (ii) and (iv) of this subparagraph: (a) Front of Maintenance Shop - On or about May 1, 2013 employees were exposed to a fire hazard due to a gasoline tank, Class 1A flammable liquid, being stored less than 20 feet from building. A permanent 2,000 gallon gasoline tank was located 75 inches from the building. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100106 G03 IV D |
Issuance Date |
2013-07-01 |
Abatement Due Date |
2013-08-16 |
Current Penalty |
2100.0 |
Initial Penalty |
2100.0 |
Final Order |
2013-09-17 |
Nr Instances |
3 |
Nr Exposed |
8 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.106(g)(3)(iv)(d): The dispensing units, except those attached to containers, shall be mounted either on a concrete island or protected against collision damage by suitable means. (a) Front of Maintenance Shop - On or about May 1, 2013 employees were exposed to a fire hazard due to gasoline liquid dispensing unit, Class 1A flammable, was not protected against vehicle collision damage. |
|
Citation ID |
01003A |
Citaton Type |
Serious |
Standard Cited |
19100110 F02 I |
Issuance Date |
2013-07-01 |
Abatement Due Date |
2013-08-16 |
Current Penalty |
2100.0 |
Initial Penalty |
2100.0 |
Final Order |
2013-09-17 |
Nr Instances |
8 |
Nr Exposed |
8 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.110(f)(2)(i): Containers in storage shall be located so as to minimize exposure to excessive temperature rise, physical damage, or tampering by unauthorized persons. (a) Maintenance Shop - On or about May 1, 2013 employees were exposed to a fire hazard from the storage of propane gas tanks inside building. |
|
Citation ID |
01003B |
Citaton Type |
Serious |
Standard Cited |
19100110 F05 V |
Issuance Date |
2013-07-01 |
Abatement Due Date |
2013-07-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2013-09-17 |
Nr Instances |
8 |
Nr Exposed |
8 |
Related Event Code (REC) |
Complaint |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.110(f)(5)(v): Such rooms shall have no open flames for heating or lighting. (a) Maintenance Shop - On or about May 1, 2013 employees were exposed to a fire hazard when smoking was permitted near propane gas heater with three 5 gallon propane tanks. |
|
Citation ID |
01004 |
Citaton Type |
Serious |
Standard Cited |
19100303 F02 |
Issuance Date |
2013-07-01 |
Abatement Due Date |
2013-07-12 |
Current Penalty |
2100.0 |
Initial Penalty |
2100.0 |
Final Order |
2013-09-17 |
Nr Instances |
8 |
Nr Exposed |
8 |
Related Event Code (REC) |
Complaint |
Gravity |
1 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. (a) Far Wall of Maintenance Shop - On or about May 1, 2013 employees were exposed to hazard of electric shock due to a circuit breaker box not being labeled for emergency shut-off. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19101200 F09 |
Issuance Date |
2013-07-01 |
Abatement Due Date |
2013-07-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2013-09-17 |
Nr Instances |
1 |
Nr Exposed |
8 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(f)(9): The employer shall ensure that labels or other forms of warning are legible, in English, and prominently displayed on the container, or readily available in the work area throughout each work shift. Employers having employees who speak other languages may add the information in their language to the material presented, as long as the information is presented in English as well. (a) Jobsite - 10,000 gallon tank of class II diesel fuel was not labeled as "Diesel Fuel." |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19101200 G08 |
Issuance Date |
2013-07-01 |
Abatement Due Date |
2013-08-16 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2013-09-17 |
Nr Instances |
1 |
Nr Exposed |
8 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.1200(g)(8): The employer shall maintain in the workplace copies of the required material safety data sheets for each hazardous chemical, and shall ensure that they are readily accessible during each work shift to employees when they are in their work area(s). (Electronic access, microfiche, and other alternatives to maintaining paper copies of the material safety data sheets are permitted as long as no barriers to immediate employee access in each workplace are created by such options.) (a) Jobsite - On or about May 1, 2013 the employer did not maintain safety data sheets for gasoline, diesel fuel, waste oil, and hydraulic fluid. |
|
|