Search icon

J. Logging, LLC

Company Details

Name: J. Logging, LLC
Jurisdiction: MISSISSIPPI
Business Type: Limited Liability Company
Status: Dissolved
Effective Date: 26 Mar 2012 (13 years ago)
Business ID: 998246
ZIP code: 39180
County: Warren
State of Incorporation: MISSISSIPPI
Principal Office Address: 315 SILVER CREEK DRIVEVICKSBURG, MS 39180

Agent

Name Role Address
Southerland, Branan P Agent 1120 Jackson Street, Vicksburg, MS 39183

Member

Name Role Address
Judy McCool Member 315 Silver Creek Dr., Vicksburg, MS 39180

Filings

Type Status Filed Date Description
Admin Dissolution Filed 2020-11-27 Action of J. Logging, LLC: AR
Notice to Dissolve/Revoke Filed 2020-08-28 Notice to Dissolve/Revoke
Annual Report LLC Filed 2019-03-06 Annual Report For J. Logging, LLC
Annual Report LLC Filed 2018-01-09 Annual Report For J. Logging, LLC
Annual Report LLC Filed 2017-01-17 Annual Report For J. Logging, LLC
Annual Report LLC Filed 2016-02-15 Annual Report For J. Logging, LLC
Annual Report LLC Filed 2015-02-09 Annual Report For J. Logging, LLC
Annual Report LLC Filed 2014-02-03 Annual Report LLC
Annual Report LLC Filed 2013-02-08 Annual Report LLC
Formation Form Filed 2012-03-26 Formation

OSHA's Inspections within Industry

Inspection Nr Report ID Date Opened Site Address
339036089 0419400 2013-05-01 6745 HWY 61 NORTH, VICKSBURG, MS, 39183
Inspection Type Complaint
Scope Complete
Safety/Health Safety
Close Conference 2013-05-01
Case Closed 2014-05-30

Related Activity

Type Complaint
Activity Nr 815350
Safety Yes

Violation Items

Citation ID 01001
Citaton Type Serious
Standard Cited 19100106 D06 I
Issuance Date 2013-07-01
Abatement Due Date 2013-08-16
Current Penalty 2800.0
Initial Penalty 2800.0
Final Order 2013-09-17
Nr Instances 8
Nr Exposed 8
Related Event Code (REC) Complaint
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.106(d)(6)(i): "General." Storage outside buildings shall be in accordance with Table H-16 or H-17, and subdivisions (ii) and (iv) of this subparagraph: (a) Front of Maintenance Shop - On or about May 1, 2013 employees were exposed to a fire hazard due to a gasoline tank, Class 1A flammable liquid, being stored less than 20 feet from building. A permanent 2,000 gallon gasoline tank was located 75 inches from the building.
Citation ID 01002
Citaton Type Serious
Standard Cited 19100106 G03 IV D
Issuance Date 2013-07-01
Abatement Due Date 2013-08-16
Current Penalty 2100.0
Initial Penalty 2100.0
Final Order 2013-09-17
Nr Instances 3
Nr Exposed 8
Related Event Code (REC) Complaint
Gravity 1
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.106(g)(3)(iv)(d): The dispensing units, except those attached to containers, shall be mounted either on a concrete island or protected against collision damage by suitable means. (a) Front of Maintenance Shop - On or about May 1, 2013 employees were exposed to a fire hazard due to gasoline liquid dispensing unit, Class 1A flammable, was not protected against vehicle collision damage.
Citation ID 01003A
Citaton Type Serious
Standard Cited 19100110 F02 I
Issuance Date 2013-07-01
Abatement Due Date 2013-08-16
Current Penalty 2100.0
Initial Penalty 2100.0
Final Order 2013-09-17
Nr Instances 8
Nr Exposed 8
Related Event Code (REC) Complaint
Gravity 1
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.110(f)(2)(i): Containers in storage shall be located so as to minimize exposure to excessive temperature rise, physical damage, or tampering by unauthorized persons. (a) Maintenance Shop - On or about May 1, 2013 employees were exposed to a fire hazard from the storage of propane gas tanks inside building.
Citation ID 01003B
Citaton Type Serious
Standard Cited 19100110 F05 V
Issuance Date 2013-07-01
Abatement Due Date 2013-07-10
Current Penalty 0.0
Initial Penalty 0.0
Final Order 2013-09-17
Nr Instances 8
Nr Exposed 8
Related Event Code (REC) Complaint
Gravity 5
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.110(f)(5)(v): Such rooms shall have no open flames for heating or lighting. (a) Maintenance Shop - On or about May 1, 2013 employees were exposed to a fire hazard when smoking was permitted near propane gas heater with three 5 gallon propane tanks.
Citation ID 01004
Citaton Type Serious
Standard Cited 19100303 F02
Issuance Date 2013-07-01
Abatement Due Date 2013-07-12
Current Penalty 2100.0
Initial Penalty 2100.0
Final Order 2013-09-17
Nr Instances 8
Nr Exposed 8
Related Event Code (REC) Complaint
Gravity 1
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. (a) Far Wall of Maintenance Shop - On or about May 1, 2013 employees were exposed to hazard of electric shock due to a circuit breaker box not being labeled for emergency shut-off.
Citation ID 02001
Citaton Type Other
Standard Cited 19101200 F09
Issuance Date 2013-07-01
Abatement Due Date 2013-07-10
Current Penalty 0.0
Initial Penalty 0.0
Final Order 2013-09-17
Nr Instances 1
Nr Exposed 8
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.1200(f)(9): The employer shall ensure that labels or other forms of warning are legible, in English, and prominently displayed on the container, or readily available in the work area throughout each work shift. Employers having employees who speak other languages may add the information in their language to the material presented, as long as the information is presented in English as well. (a) Jobsite - 10,000 gallon tank of class II diesel fuel was not labeled as "Diesel Fuel."
Citation ID 02002
Citaton Type Other
Standard Cited 19101200 G08
Issuance Date 2013-07-01
Abatement Due Date 2013-08-16
Current Penalty 0.0
Initial Penalty 0.0
Final Order 2013-09-17
Nr Instances 1
Nr Exposed 8
Related Event Code (REC) Complaint
FTA Current Penalty 0.0
Citation text line 29 CFR 1910.1200(g)(8): The employer shall maintain in the workplace copies of the required material safety data sheets for each hazardous chemical, and shall ensure that they are readily accessible during each work shift to employees when they are in their work area(s). (Electronic access, microfiche, and other alternatives to maintaining paper copies of the material safety data sheets are permitted as long as no barriers to immediate employee access in each workplace are created by such options.) (a) Jobsite - On or about May 1, 2013 the employer did not maintain safety data sheets for gasoline, diesel fuel, waste oil, and hydraulic fluid.

Date of last update: 25 Mar 2025

Sources: Mississippi Secretary of State